FM-200 / HFC Clean Agent vs FK-5-1-12 Clean Agent

Comparison Guide

FM-200 / HFC Clean Agent vs FK-5-1-12 Clean Agent

Oct 2026

Compare FM-200 / HFC-227ea with FK-5-1-12: agent identity, physical properties, design requirements, room integrity and the documents to request before installation.

Quick answer

FM-200 is a trade name for HFC-227ea, a hydrofluorocarbon extinguishing agent. FK-5-1-12 is a fluoroketone; Novec 1230 is a 3M trade name associated with this chemistry. These are different agents, with different physical properties and system-design requirements. Compare an engineered system and its documented lifecycle support, rather than choosing by brand name alone.

FM-200 and FK-5-1-12: practical differences

Selection factor FM-200 / HFC-227ea FK-5-1-12
Chemical family Hydrofluorocarbon: heptafluoropropane. Fluoroketone: dodecafluoro-2-methylpentan-3-one.
Trade name versus agent identity FM-200 is a Chemours trademark for HFC-227ea. FK-5-1-12 is an agent designation. Novec 1230 is a 3M trademark; verify the actual fluid manufacturer and supply documentation.
At normal atmospheric pressure A gas at ordinary room temperature; manufacturer data gives a boiling point of approximately −16.3°C. A liquid at ordinary room temperature; manufacturer data gives a boiling point of approximately 49°C.
Storage in an engineered system Uses the selected OEM’s approved container, fill density, valve and pressurization arrangement. Uses the selected OEM’s approved container, fill density, valve and pressurization arrangement. Equipment compatibility must be confirmed for this agent.
Environmental comparison The published Chemours bulletin reports zero ozone-depletion potential and a higher global-warming potential than the cited FK-5-1-12 data. The cited JCI datasheet reports zero ozone-depletion potential and a global-warming potential of 1. Confirm the assessment basis and current product documents.
Agent quantity and piping Calculate for the hazard, protected volume, temperature and approved HFC-227ea system. Calculate separately using the approved FK-5-1-12 system. Do not transfer another agent’s cylinder quantity or hydraulic results.
Enclosure and interfaces Both options require coordinated room boundaries, HVAC interfaces, release controls, retention criteria and commissioning under the approved fire strategy.

What to check before selecting a system

  1. Define the protected space: room dimensions, relevant floor/ceiling voids, minimum temperature, occupancy and the actual fire hazard.
  2. Request the design basis: selected agent, applicable standards and editions, design concentration, agent quantity and OEM hydraulic calculations.
  3. Check installation constraints: cylinder location, pipe route, nozzle arrangement, access for maintenance and pressure-relief requirements.
  4. Coordinate operation: detection, pre-discharge warning, evacuation, HVAC shutdown, releasing controls and manual/abort functions where specified.
  5. Plan acceptance and support: enclosure-integrity assessment, integrated tests, records, training, maintenance and documented recharge arrangements.

Frequently asked questions

Can FK-5-1-12 simply replace FM-200 in an existing installation?

Do not assume interchangeability. Have the proposed agent, containers, valves, piping, nozzles, controls and calculations checked against the selected OEM’s approved design. A change of agent requires a documented engineering review.

Does the agent name prove that a complete system is approved?

No. Verify the specified system and its components, the manufacturer documentation and the approvals required by the project. An agent trade name alone does not establish equipment compatibility.

Which option is appropriate for an occupied room?

Review the actual design concentration, exposure conditions, evacuation arrangements and current manufacturer instructions. An occupied-room application needs project-specific assessment; neither product name is a blanket safety guarantee.

Discuss a clean-agent requirement with Vasu

For a Pune or India project, share the location, room layout, dimensions, intended application and relevant specifications. Explore Vasu’s clean-agent design and installation services, read about room integrity, or request a technical discussion.

Primary technical references

These references describe specific agents and systems. Confirm current supply, applicable requirements and the selected OEM’s latest approved documentation for the actual project.